Standards & guidance.

From design references to acceptance criteria.

A catalog of Chinese national, industry and association standards, alongside international and overseas references, for AI data centers, liquid cooling and energy infrastructure. Start with the problem, then check editions, status and original clauses.

HOW TO READ

Understand the hierarchy,
then choose your references.

  1. 01Check the subject and scope

    Facilities, systems, racks and coolants have different scopes of application.

  2. 02Check publication and implementation

    Published documents awaiting implementation, current documents and drafts are labeled separately.

  3. 03Return to the original clauses

    Reading notes help you select references. Engineering use depends on the official text and applicable conditions.

FIND YOUR REFERENCE

Standards catalog

Status reflects the review-date snapshot. Guidance and work in progress have separate types or status labels.

44 references

China / National standardCurrent

GB 50174-2017

Code for Design of Data Centers

Ministry of Housing and Urban-Rural Development

Design & constructionCooling & thermal managementPower supply & distribution

Applies to the design of new, renovated and expanded data centers. It provides a national-standard reference for reviewing site selection, buildings and supporting infrastructure.

Reading note

The current published document is the Code for Design of Data Centers; the 2026 consultation draft titled Standard for Design of Data Centers must be identified separately.

Published
2017-05-04
Effective
2018-01-01
Requirement status
Requirement status to be confirmed
Sources, edition & access

This English title is an editorial reference translation, not an official English edition. Verify the official title and text before use.

Official record · Current status, dates and scope are verified against the National Library of Standards record and corroborated by ministry documents. The relationship between individual mandatory provisions and general codes has not been checked clause by clause, so mandatory applicability remains unverified; obtain the full text through official or licensed channels. The English title is translated for reference and does not imply an official English edition.

  1. National Library of Standards: GB 50174-2017, Code for Design of Data Centers ↗

    The record explicitly marks the standard as current and confirms its designation, title, issue date of 2017-05-04, effective date of 2018-01-01, and applicability to new, renovated and expanded data centers.

  2. Ministry of Housing and Urban-Rural Development: Standards Framework for Urban Digital Public Infrastructure ↗

    The framework attached to the notice lists the Code for Design of Data Centers as current; the specific edition and dates are cross-checked against the National Library of Standards record.

  3. Ministry of Housing and Urban-Rural Development: Consultation Notice for the Standard for Design of Data Centers ↗

    The document issued on 2026-01-09 and made public on 2026-01-14 is a consultation draft, not a newly published or effective edition.

Official referenceChecked 2026-11-01
China / National standardCurrent

GB 40879-2021

Minimum Allowable Values of Energy Efficiency and Energy Efficiency Grades for Data Centers

State Administration for Market Regulation; Standardization Administration of China

Energy efficiency & carbonTesting & measurementOperations & acceptance

Specifies energy efficiency grades and testing and calculation requirements for data centers. The 2021 edition covers individual buildings or modular units using air cooling and electrically driven air conditioning; liquid-cooled projects must check applicability.

Reading note

Confirm the cooling method and measurement boundary before applying the grades; a revision project does not establish that a new edition is in force.

Published
2021-10-11
Effective
2022-11-01
Requirement status
Mandatory standard
Sources, edition & access

This English title is an editorial reference translation, not an official English edition. Verify the official title and text before use.

Official open full text · The National Standards Full-text Disclosure System lists online preview and download options; follow the conditions on the official page. This site does not mirror the full standard. The English title is translated for reference and does not imply an official English edition.

  1. National Standards Full-text Disclosure System: GB 40879-2021 ↗

    The official record marks the standard as current and confirms its title, issue date of 2021-10-11, effective date of 2022-11-01 and issuing bodies.

  2. National Standard Revision Project: Scope of the GB 40879 Revision ↗

    The official revision-project description confirms that the current 2021 edition is limited to air cooling and electrically driven air conditioning and excludes cooling in which liquid replaces air as the medium; this page describes a revision project, not a newly published standard.

Official referenceChecked 2026-11-01
China / National standardCurrent

GB/T 51314-2018

Standard for Operation and Maintenance of Data Center Infrastructure

Ministry of Housing and Urban-Rural Development

Operations & acceptanceCooling & thermal managementPower supply & distribution

Applies to data centers already in operation and provides a basis for systematic management of infrastructure operation and maintenance. It can support operating procedures and reviews of infrastructure support requirements.

Reading note

Translate infrastructure operation and maintenance requirements into procedures and records linked to project design and acceptance documents.

Published
2018-09-11
Effective
2019-03-01
Requirement status
Recommended standard
Sources, edition & access

This English title is an editorial reference translation, not an official English edition. Verify the official title and text before use.

Official record · Because the ministry's original publication page is intermittently accessible, status and dates are verified against the National Library of Standards record of the China National Institute of Standardization; the ministry's standards framework provides corroboration. Obtain the full text through official publication, on-site library access or licensed channels. The English title is translated for reference and does not imply an official English edition.

  1. National Library of Standards: GB/T 51314-2018, Standard for Operation and Maintenance of Data Center Infrastructure ↗

    The record explicitly marks the standard as current and confirms its designation, title, issue date of 2018-09-11, effective date of 2019-03-01, and applicability to operating data centers.

  2. Ministry of Housing and Urban-Rural Development: Standards Framework for Urban Digital Public Infrastructure ↗

    The framework attached to the notice lists the Standard for Operation and Maintenance of Data Center Infrastructure as current; the specific edition and dates are cross-checked against the National Library of Standards record.

Official referenceChecked 2026-11-01
China / National standardCurrent

GB/T 44989-2024

Evaluation of Green Data Centers

State Administration for Market Regulation; Standardization Administration of China

Energy efficiency & carbonWater resourcesOperations & acceptanceTesting & measurement

Supports evaluation of data center environmental performance and improvements in construction and operation, covering energy and resource use and green management. It provides a reference for preparing self-assessment, external assessment and diagnostic evaluation materials.

Reading note

A green assessment requires comprehensive evidence of energy and resource use and operational management, beyond a single energy efficiency value.

Published
2024-11-28
Effective
2025-06-01
Requirement status
Recommended standard
Sources, edition & access

This English title is an editorial reference translation, not an official English edition. Verify the official title and text before use.

Official open full text · The National Standards Full-text Disclosure System lists online preview and download options; follow the conditions on the official page. This site does not mirror the full standard. The English title is translated for reference and does not imply an official English edition.

  1. National Standards Full-text Disclosure System: GB/T 44989-2024 ↗

    The official record confirms current status, an issue date of 2024-11-28 and an effective date of 2025-06-01.

  2. Ministry of Industry and Information Technology: Accelerating the Development of National Green Computing Facilities ↗

    The official article states that GB/T 44989 took effect on 2025-06-01 and provides a basis for green data center construction, operation, maintenance and improvement.

Official referenceChecked 2026-11-01
China / National standardCurrent

GB/T 32910.3-2016

Data Centers — Resource Utilization — Part 3: Electrical Energy Efficiency Requirements and Measurement Methods

Former General Administration of Quality Supervision, Inspection and Quarantine; Standardization Administration of China

Energy efficiency & carbonTesting & measurementOperations & acceptance

Sets energy efficiency requirements and measurement methods for electricity use in data centers. It provides a methodological reference for energy metering, operational efficiency analysis and comparisons before and after retrofits.

Reading note

Use consistent measurement boundaries, reporting periods and operating load conditions when comparing energy efficiency.

Published
2016-08-29
Effective
2017-03-01
Requirement status
Recommended standard
Sources, edition & access

This English title is an editorial reference translation, not an official English edition. Verify the official title and text before use.

Official open full text · The National Standards Full-text Disclosure System lists online preview and download options; follow the conditions on the official page. This site does not mirror the full standard. The English title is translated for reference and does not imply an official English edition.

  1. National Standards Full-text Disclosure System: GB/T 32910.3-2016 ↗

    The record for the published Chinese edition confirms current status, an issue date of 2016-08-29 and an effective date of 2017-03-01; the 2024 publication date of a foreign-language edition must not be treated as a revision year for the Chinese edition.

Official referenceChecked 2026-11-01
China / National standardCurrent

GB/T 32910.6-2025

Data Centers — Resource Utilization — Part 6: Water Resource Use Efficiency

State Administration for Market Regulation; Standardization Administration of China

Water resourcesTesting & measurementOperations & acceptance

Addresses calculation and evaluation of water resource use efficiency in data centers. It supports water-use analysis and consistent metrics when comparing design, construction, operation, maintenance and water-saving retrofit options.

Reading note

When reporting WUE, state the water-use boundary, the IT equipment energy denominator and the reporting period.

Published
2025-05-30
Effective
2025-12-01
Requirement status
Recommended standard
Sources, edition & access

This English title is an editorial reference translation, not an official English edition. Verify the official title and text before use.

Official open full text · The National Standards Full-text Disclosure System lists online preview and download options; follow the conditions on the official page. This site does not mirror the full standard. The English title is translated for reference and does not imply an official English edition.

  1. National Standards Full-text Disclosure System: GB/T 32910.6-2025 ↗

    The official record confirms the title as water resource use efficiency, current status, an issue date of 2025-05-30 and an effective date of 2025-12-01.

  2. National Standards Information Platform: GB/T 32910.6-2025 ↗

    The published-standard record classifies the document as a method standard under the National Information Technology Standardization Technical Committee.

Official referenceChecked 2026-11-01
China / National standardCurrent

GB/T 45837-2025

Evaluation Method for Integrated Energy Utilization in Data Centers

State Administration for Market Regulation; Standardization Administration of China

Energy efficiency & carbonTesting & measurementOperations & acceptance

Establishes evaluation grades for integrated energy utilization in data centers and specifies indicators, management requirements and evaluation methods. It applies to key performance indicator assessment, energy conservation monitoring and grading of integrated energy utilization.

Reading note

Assess integrated energy utilization using the full set of indicators and management evidence, and check retrofit performance with a consistent evaluation method.

Published
2025-06-30
Effective
2026-01-01
Requirement status
Recommended standard
Sources, edition & access

This English title is an editorial reference translation, not an official English edition. Verify the official title and text before use.

Official open full text · The National Standards Full-text Disclosure System lists online preview and download options; follow the conditions on the official page. This site does not mirror the full standard. The English title is translated for reference and does not imply an official English edition.

  1. National Standards Full-text Disclosure System: GB/T 45837-2025 ↗

    The official record confirms current status, an issue date of 2025-06-30 and an effective date of 2026-01-01.

  2. National Standards Information Platform: Explanation of GB/T 45837-2025 ↗

    The official course description outlines the evaluation grades, indicators, management requirements for integrated energy utilization and scope of application.

Official referenceChecked 2026-11-01
China / National standardPublished · Not yet effective

GB/T 48023-2026

Technical Specification for Cold-plate Liquid Cooling Systems in Data Centers

State Administration for Market Regulation; Standardization Administration of China

Cooling & thermal managementDesign & constructionOperations & acceptance

A national technical specification for cold-plate liquid cooling systems in data centers, providing a reference for liquid cooling design and system integration. It has been issued and will take effect on 2027-02-01.

Reading note

It may inform technical preparation, but must be identified as issued and not yet in force before 2027-02-01.

Published
2026-07-30
Effective
2027-02-01
Requirement status
Recommended standard
Sources, edition & access

This English title is an editorial reference translation, not an official English edition. Verify the official title and text before use.

Official open full text · The National Standards Full-text Disclosure System lists online preview and download options; follow the conditions on the official page. This site does not mirror the full standard. The English title is translated for reference and does not imply an official English edition.

  1. National Standards Full-text Disclosure System: GB/T 48023-2026 ↗

    The official record explicitly marks the standard as not yet in force, with an issue date of 2026-07-30 and an effective date of 2027-02-01; it must not be described as already effective.

Official referenceChecked 2026-11-01
China / National standardPublished · Not yet effective

GB/T 48097-2026

General Specification for Cold-plate Liquid-cooled Cabinets in Data Centers

State Administration for Market Regulation; Standardization Administration of China

Cooling & thermal managementDesign & construction

A general national specification for cold-plate liquid-cooled cabinets in data centers, supporting technical preparation for equipment selection and cabinet integration. It takes effect on 2027-03-01 and is not yet in force.

Reading note

Cabinet development may refer to the published text in advance, while procurement and compliance documents must state that it is not yet in force.

Published
2026-08-28
Effective
2027-03-01
Requirement status
Recommended standard
Sources, edition & access

This English title is an editorial reference translation, not an official English edition. Verify the official title and text before use.

Official open full text · The National Standards Full-text Disclosure System lists online preview and download options; follow the conditions on the official page. This site does not mirror the full standard. The English title is translated for reference and does not imply an official English edition.

  1. National Standards Full-text Disclosure System: GB/T 48097-2026 ↗

    The official record explicitly marks the standard as not yet in force, confirms an issue date of 2026-08-28 and an effective date of 2027-03-01, and classifies it as a recommended national standard.

Official referenceChecked 2026-11-01
China / Industry standardCurrent

YD/T 4024-2022

General Technical Requirements and Test Methods for Liquid-cooled Server Systems in Data Centers

Ministry of Industry and Information Technology; China Communications Standards Association responsible for standardization coordination

Cooling & thermal managementDesign & constructionOperations & acceptanceTesting & measurement

Specifies general technical requirements and test methods for liquid-cooled server systems in data centers. It guides liquid cooling system design, construction, deployment, operation and maintenance.

Reading note

Use the general standard to establish system boundaries before applying specific standards for cold-plate cooling, immersion cooling and coolants.

Published
2022-04-24
Effective
2022-07-01
Requirement status
Recommended standard
Sources, edition & access

This English title is an editorial reference translation, not an official English edition. Verify the official title and text before use.

Official record · The official platform provides bibliographic and status information; full-text access and use are subject to the official page's conditions. This site does not store the full standard. The English title is translated for reference and does not imply an official English edition.

  1. National Standards Information Platform: YD/T 4024-2022 ↗

    The official record explicitly identifies a recommended standard that is current, issued on 2022-04-24 and effective from 2022-07-01, covering design, construction, deployment, operation and maintenance.

Official referenceChecked 2026-11-01
China / Industry standardCurrent

YD/T 3979-2021

Technical Requirements and Test Methods for Immersion Liquid-cooled Server Systems in Data Centers

Ministry of Industry and Information Technology; China Communications Standards Association responsible for standardization coordination

Cooling & thermal managementDesign & constructionOperations & acceptanceTesting & measurement

Specifies technical requirements and test methods for immersion liquid-cooled server systems in data centers. It supports technical reviews during system design, construction, deployment, operation and maintenance.

Reading note

Apply requirements and tests specific to immersion cooling rather than directly transferring cold-plate system provisions.

Published
2021-12-02
Effective
2022-04-01
Requirement status
Recommended standard
Sources, edition & access

This English title is an editorial reference translation, not an official English edition. Verify the official title and text before use.

Official record · The official platform provides bibliographic and status information; full-text access and use are subject to the official page's conditions. This site does not store the full standard. The English title is translated for reference and does not imply an official English edition.

  1. National Standards Information Platform: YD/T 3979-2021 ↗

    The official record explicitly identifies a recommended standard that is current and confirms its issue date of 2021-12-02, effective date of 2022-04-01 and scope.

Official referenceChecked 2026-10-31
China / Industry standardCurrent

YD/T 3980-2021

Technical Requirements and Test Methods for Cold-plate Liquid-cooled Server Systems in Data Centers

Ministry of Industry and Information Technology; China Communications Standards Association responsible for standardization coordination

Cooling & thermal managementDesign & constructionOperations & acceptanceTesting & measurement

Specifies technical requirements and test methods for cold-plate liquid-cooled server systems in data centers. It covers design, construction, deployment, operation, maintenance and testing for engineering applications.

Reading note

Distinguish the server-system, whole-rack and data-center levels of application and check requirements at each level.

Published
2021-12-02
Effective
2022-04-01
Requirement status
Recommended standard
Sources, edition & access

This English title is an editorial reference translation, not an official English edition. Verify the official title and text before use.

Official record · The official platform provides bibliographic and status information; full-text access and use are subject to the official page's conditions. This site does not store the full standard. The English title is translated for reference and does not imply an official English edition.

  1. National Standards Information Platform: YD/T 3980-2021 ↗

    The official record explicitly identifies a recommended standard that is current and confirms its issue date of 2021-12-02, effective date of 2022-04-01 and applicability to cold-plate liquid-cooled server systems.

Official referenceChecked 2026-10-31
China / Industry standardCurrent

YD/T 3982-2021

Technical Requirements and Test Methods for Cooling Liquids in Data Center Liquid Cooling Systems

Ministry of Industry and Information Technology; China Communications Standards Association responsible for standardization coordination

Cooling & thermal managementOperations & acceptanceTesting & measurement

Specifies technical requirements and test methods for cooling liquids used in data center liquid cooling systems. It supports technical checks throughout coolant selection, use, maintenance and testing.

Reading note

Apply dedicated coolant requirements during selection and maintenance, and check them against system and material conditions.

Published
2021-12-02
Effective
2022-04-01
Requirement status
Recommended standard
Sources, edition & access

This English title is an editorial reference translation, not an official English edition. Verify the official title and text before use.

Official record · The official platform provides bibliographic and status information; full-text access and use are subject to the official page's conditions. This site does not store the full standard. The English title is translated for reference and does not imply an official English edition.

  1. National Standards Information Platform: YD/T 3982-2021 ↗

    The official record explicitly identifies a recommended standard that is current, issued on 2021-12-02 and effective from 2022-04-01, with a scope covering liquid selection, use, maintenance and testing.

Official referenceChecked 2026-10-31
China / Industry standardCurrent

YD/T 3983-2021

Technical Requirements and Test Methods for Energy Use Efficiency of Liquid-cooled Server Systems in Data Centers

Ministry of Industry and Information Technology; China Communications Standards Association responsible for standardization coordination

Cooling & thermal managementEnergy efficiency & carbonTesting & measurement

Specifies technical requirements and test methods for energy use efficiency in liquid-cooled server systems. It supports verification of liquid cooling efficiency during system design, construction, deployment and testing.

Reading note

Define the liquid-cooled server-system boundary and test conditions before relating results to facility-level energy efficiency metrics.

Published
2021-12-02
Effective
2022-04-01
Requirement status
Recommended standard
Sources, edition & access

This English title is an editorial reference translation, not an official English edition. Verify the official title and text before use.

Official record · The official platform provides bibliographic and status information; full-text access and use are subject to the official page's conditions. This site does not store the full standard. The English title is translated for reference and does not imply an official English edition.

  1. National Standards Information Platform: YD/T 3983-2021 ↗

    The official record explicitly identifies a recommended standard that is current, issued on 2021-12-02 and effective from 2022-04-01, covering liquid cooling system design, construction, deployment and testing.

Official referenceChecked 2026-10-31
China / Industry standardCurrent

YD/T 6049-2024

Technical Requirements and Test Methods for Cold-plate Liquid-cooled Whole-rack Servers

Ministry of Industry and Information Technology; China Communications Standards Association responsible for standardization coordination

Cooling & thermal managementDesign & constructionTesting & measurement

Specifies technical requirements and test methods for cold-plate liquid-cooled whole-rack servers in data centers. It applies to design, production and testing and can inform equipment selection and verification plans.

Reading note

Test whole-rack servers against the standard for that equipment level and align the results with data-center-side interface requirements.

Published
2024-10-24
Effective
2025-02-01
Requirement status
Recommended standard
Sources, edition & access

This English title is an editorial reference translation, not an official English edition. Verify the official title and text before use.

Official record · The official platform provides bibliographic and status information; full-text access and use are subject to the official page's conditions. This site does not store the full standard. The English title is translated for reference and does not imply an official English edition.

  1. National Standards Information Platform: YD/T 6049-2024 ↗

    The official record explicitly identifies a recommended standard that is current, issued on 2024-10-24 and effective from 2025-02-01, applying to design, production and testing.

Official referenceChecked 2026-11-01
China / Industry standardCurrent

YD/T 6358-2025

Technical Requirements for Cold-plate Liquid-cooled Data Centers

Ministry of Industry and Information Technology; China Communications Standards Association responsible for standardization coordination

Cooling & thermal managementDesign & constructionOperations & acceptanceTesting & measurement

Specifies technical requirements for cold-plate liquid-cooled data centers and telecommunications equipment buildings. It covers data-center-level design, construction, deployment, use, operation, maintenance, testing and evaluation.

Reading note

When moving from a server system to an entire facility, use data-center-level standards to check engineering conditions.

Published
2025-04-10
Effective
2025-08-01
Requirement status
Recommended standard
Sources, edition & access

This English title is an editorial reference translation, not an official English edition. Verify the official title and text before use.

Official record · The official platform provides bibliographic and status information; full-text access and use are subject to the official page's conditions. This site does not store the full standard. The English title is translated for reference and does not imply an official English edition.

  1. National Standards Information Platform: YD/T 6358-2025 ↗

    The official record explicitly identifies a recommended standard that is current, issued on 2025-04-10 and effective from 2025-08-01, applying to data centers and telecommunications equipment buildings.

Official referenceChecked 2026-10-31
China / Industry standardStatus requires review

YD/T 7105-2026

Test Methods for Cold-plate Liquid-cooled Data Centers

Ministry of Industry and Information Technology; China Communications Standards Association responsible for standardization coordination

Cooling & thermal managementTesting & measurementOperations & acceptance

Describes equipment, acceptance and operation and maintenance test methods for cold-plate liquid-cooled data centers. The effective date stated in the official announcement is 2026-11-01, which has now been reached.

Reading note

Organize equipment, acceptance and operation and maintenance test evidence separately, with clear test purposes and system boundaries.

The effective date of 2026-11-01 has arrived, but the official record still displays not yet in force; status remains unconfirmed pending a platform update and recheck.

Published
2026-07-15
Effective
2026-11-01
Requirement status
Recommended standard
Sources, edition & access

This English title is an editorial reference translation, not an official English edition. Verify the official title and text before use.

Official record · The official record is public. Its cached status remains not yet in force although the stated effective date of 2026-11-01 has arrived; status awaits verification after the platform updates. Full text has not been downloaded or mirrored. The English title is translated for reference and does not imply an official English edition.

  1. National Standards Information Platform: YD/T 7105—2026 ↗

    The record identifies a recommended standard issued on 2026-07-15 and effective from 2026-11-01, covering equipment, acceptance and operation and maintenance testing; its cached page still says not yet in force, while the stated effective date has been reached at the 2026-11-01 review cutoff.

Official referenceChecked 2026-11-01
China / Industry standardStatus requires review

YD/T 7463-2026

Planning Requirements for Cold-plate Liquid-cooled Computing Centers

Ministry of Industry and Information Technology; China Communications Standards Association responsible for standardization coordination

Design & constructionCooling & thermal managementPower supply & distributionWater resources

Applies to planning new, renovated and expanded cold-plate liquid-cooled computing centers, including supercomputing and AI computing centers, and covers classification, buildings, cooling, electrical systems, intelligent systems, and water supply and drainage. It excludes phase-change cold-plate liquid cooling systems.

Reading note

Coordinate building, cooling, electrical, water supply and drainage design during planning, and first establish whether the system uses phase-change cold-plate cooling.

The effective date of 2026-11-01 has arrived, but the official record still displays not yet in force; status remains unconfirmed pending a platform update and recheck.

Published
2026-07-15
Effective
2026-11-01
Requirement status
Recommended standard
Sources, edition & access

This English title is an editorial reference translation, not an official English edition. Verify the official title and text before use.

Official record · The official record is public. Its cached status remains not yet in force although the stated effective date of 2026-11-01 has arrived; status awaits verification after the platform updates. Phase-change cold-plate liquid cooling systems are excluded, and full text has not been downloaded or mirrored. The English title is translated for reference and does not imply an official English edition.

  1. National Standards Information Platform: YD/T 7463—2026 ↗

    The record identifies a recommended standard issued on 2026-07-15 and effective from 2026-11-01, covering new, renovated and expanded computing centers, including AI and supercomputing facilities, while excluding phase-change cold-plate systems; its cached status remains not yet in force although the effective date has arrived.

Official referenceChecked 2026-11-01
China / Association standardCurrent

T/CAR 24-2025

Technical specification for pumped two phase direct liquid cooling system to chips of data center

Chinese Association of Refrigeration

Cooling & thermal managementDesign & constructionTesting & measurement

Specifies system requirements and engineering acceptance provisions for pumped two-phase cold-plate liquid cooling in data centers. It supports design, equipment selection and delivery reviews for two-phase systems.

Reading note

Use it to check system requirements and acceptance boundaries for two-phase cold-plate projects.

Published
2025-07-31
Effective
2025-09-01
Requirement status
Adoption depends on the project
Sources, edition & access

Technical specification for pumped two phase direct liquid cooling system to chips of data center

Official record · The platform provides an official record and states that the full text is neither public nor available for sale. The formal issue date is 2025-07-31; 2025-11-04 is the platform posting date.

  1. National Platform for Association Standards Information: T/CAR 24-2025 ↗

    The platform marks the standard as current, formally issued on 2025-07-31 and effective from 2025-09-01; it was posted on the platform on 2025-11-04, and its technical content covers system requirements and acceptance.

Official referenceChecked 2026-10-31
China / Association standardCurrent

T/DZJN 524-2026

Design Requirements for Liquid-cooled Data Centers

China Electronics Energy Saving Technology Association

Cooling & thermal managementDesign & constructionPower supply & distributionWater resourcesEnergy efficiency & carbon

Applies to new, renovated and expanded data centers using single-phase cold-plate or single-phase immersion liquid cooling. It covers structural, cooling, electrical, monitoring, water supply and drainage, fire protection and waste heat recovery design.

Reading note

Check design interfaces across the building and mechanical and electrical systems when planning single-phase liquid-cooled data centers.

Published
2026-04-13
Effective
2026-05-16
Requirement status
Adoption depends on the project
Sources, edition & access

This English title is an editorial reference translation, not an official English edition. Verify the official title and text before use.

Official record · Provides the official record and a link to the publication announcement. The formal issue date is 2026-04-13, which must be distinguished from the platform posting date of 2026-04-22. The English title is translated for reference and does not imply an official English edition.

  1. National Platform for Association Standards Information: T/DZJN 524-2026 ↗

    The platform marks the standard as current, formally issued on 2026-04-13 and effective from 2026-05-16; it was posted on the platform on 2026-04-22, and covers single-phase cold-plate and single-phase immersion cooling.

Official referenceChecked 2026-10-31
China / Association standardCurrent

T/DZJN 386-2025

Cooling design requirements for artificial intelligence data center

China Electronics Energy Saving Technology Association

Cooling & thermal managementDesign & constructionEnergy efficiency & carbonWater resourcesTesting & measurement

Applies to cooling system design for new, renovated and expanded AI data centers and to other data centers hosting computing services. It covers terminal equipment, cooling sources, monitoring, supporting facilities, heat recovery and energy efficiency evaluation.

Reading note

Evaluate terminal equipment, cooling sources, energy use and water use together when reviewing AI data center cooling options.

Published
2025-01-15
Effective
2025-01-17
Requirement status
Adoption depends on the project
Sources, edition & access

Cooling design requirements for artificial intelligence data center

Official open full text · The National Platform for Association Standards Information provides a link to read the published PDF on the source website. This site does not copy or mirror the full text.

  1. National Platform for Association Standards Information: Published Text of T/DZJN 386-2025 ↗

    The published text's cover gives an issue date of 2025-01-15 and an effective date of 2025-01-17; its scope and contents cover terminal equipment, cooling sources, monitoring, heat recovery and energy efficiency evaluation.

  2. National Library of Standards: Drafting-organization Search Results Including T/DZJN 386-2025 ↗

    The search results list T/DZJN 386-2025 separately, marking it as current and giving an issue date of 2025-01-15.

Official referenceChecked 2026-10-31
China / Association standardCurrent

T/CIE 342-2025

Guidelines for Operation and Maintenance of Indirect Cold-plate Liquid Cooling Systems in Data Centers

Chinese Institute of Electronics

Cooling & thermal managementOperations & acceptanceWater resources

Addresses installation, commissioning, routine maintenance and emergency response for indirect cold-plate liquid cooling systems. It primarily covers server loops using deionized water and external loops using softened water; systems using other cooling fluids may refer to it.

Reading note

Identify the fluids in the internal and external loops and their management boundaries before developing operation and maintenance procedures.

Published
2025-09-09
Effective
2025-10-01
Requirement status
Adoption depends on the project
Sources, edition & access

This English title is an editorial reference translation, not an official English edition. Verify the official title and text before use.

Official record · Provides the official record. The platform posting date is 2026-01-08, while the standard's formal issue date is 2025-09-09. The English title is translated for reference and does not imply an official English edition.

  1. National Platform for Association Standards Information: T/CIE 342-2025 ↗

    The platform marks the standard as current, issued on 2025-09-09 and effective from 2025-10-01; it was posted on the platform on 2026-01-08, and its scope describes operation, maintenance, commissioning, emergency response and fluid conditions.

Official referenceChecked 2026-11-01
China / Association standardCurrent

T/CESA 1249.1-2023

Technical specification for the liquid cooling devices in a server and storage equipment – Part 1: Cold plate

China Electronics Standardization Association

Cooling & thermal managementDesign & constructionTesting & measurement

Specifies design, structural, thermal performance and environmental adaptability requirements and test methods for single-phase liquid cooling cold plates used in servers and storage equipment. It supports cold-plate manufacturing, testing and evaluation, procurement and maintenance.

Reading note

Include structural requirements, thermal performance and corresponding verification methods together in cold-plate procurement specifications.

Published
2023-02-28
Effective
2023-03-15
Requirement status
Adoption depends on the project
Sources, edition & access

Technical specification for the liquid cooling devices in a server and storage equipment – Part 1: Cold plate

Official open full text · The issuing association's Open Computing Technology Committee provides the PDF on its official website. Use is subject to the issuing body's copyright terms; this site only links to the original.

  1. National Library of Standards: T/CESA 1249.1-2023 ↗

    The specific record marks the standard as current, issued on 2023-02-28 and effective from 2023-03-15, and describes its applicability to design, manufacturing, testing and evaluation of single-phase liquid cooling cold plates.

  2. China Electronics Standardization Association, Open Computing Technology Committee: Published Text of T/CESA 1249.1-2023 ↗

    The association committee publicly provides the published PDF on its own website; the cover dates match the National Library of Standards record, and the contents list design, structural, thermal performance and environmental adaptability tests.

Official referenceChecked 2026-11-01
China / Association standardCurrent

T/CESA 1249.3-2023

Technical specification for the liquid cooled components in server and storage equipment - Part 3: coolant distribution unit

China Electronics Standardization Association

Cooling & thermal managementDesign & constructionOperations & acceptanceTesting & measurement

Covers coolant distribution units for servers and storage equipment, including structure, maintenance, safety, interfaces, heat transfer and operating performance, reliability, testing and assessment. It supports design, manufacturing, procurement, evaluation, operation and maintenance.

Reading note

Check rated conditions, heat transfer performance, interfaces and reliability verification together when selecting a CDU.

Published
2023-10-31
Effective
2023-10-31
Requirement status
Adoption depends on the project
Sources, edition & access

Technical specification for the liquid cooled components in server and storage equipment - Part 3: coolant distribution unit

Official open full text · The association committee's official website publicly provides the published PDF. The date of 2023-10-31 agrees between the published text and the National Library of Standards record; the date 20231030 in an earlier announcement attachment is not used.

  1. National Library of Standards: T/CESA 1249.3-2023 ↗

    The specific record marks the standard as current, with both issue and effective dates of 2023-10-31; it applies to design, manufacturing and evaluation, with reference use for procurement, operation and maintenance.

  2. China Electronics Standardization Association, Open Computing Technology Committee: Published Text of T/CESA 1249.3-2023 ↗

    The published PDF cover gives both issue and effective dates as 2023-10-31; its scope covers CDU structure, safety, functions, performance, reliability, testing and quality assessment.

Official referenceChecked 2026-11-01
China / Association standardCurrent

T/CCSA 269-2019

General technical requirements and test methods for liquid cooling server system of data center

China Communications Standards Association

Cooling & thermal managementDesign & constructionOperations & acceptanceTesting & measurement

Sets general system requirements and verification methods for liquid-cooled data center servers and their supporting operating conditions. It guides liquid cooling system design, construction, deployment, operation and maintenance.

Reading note

System-level liquid cooling assessments should cover both servers and their supporting operating conditions.

Published
2019-12-23
Effective
2019-12-23
Requirement status
Adoption depends on the project
Sources, edition & access

General technical requirements and test methods for liquid cooling server system of data center

Full text requires authorized access · The National Library of Standards provides an official record and a link to licensed purchase; the paid full text has not been obtained or mirrored. Related YD/T industry standards do not automatically supersede this association standard.

  1. National Library of Standards: T/CCSA 269-2019 ↗

    The indexed content of the specific official record marks the standard as current, with both issue and effective dates of 2019-12-23, and gives its general system scope and the China Communications Standards Association's standardization coordination role.

  2. Open Data Center Committee: ODCC Testing and Evaluation Supports a New IT Ecosystem ↗

    The official ODCC article explicitly identifies T/CCSA 269 as an association standard for liquid-cooled data center server systems published on the basis of an ODCC project.

Official referenceChecked 2026-10-31
China / Association standardCurrent

T/CCSA 272-2019

Technical requirements and test methods for immersion liquid cooling server system of data center

China Communications Standards Association

Cooling & thermal managementDesign & constructionOperations & acceptanceTesting & measurement

Specifies technical requirements and test methods for immersion liquid-cooled data center servers and their supporting operating conditions. It supports technical checks during immersion system design, construction, deployment, operation and maintenance.

Reading note

Verification of immersion cooling should cover both servers and their supporting operating conditions.

Published
2019-12-23
Effective
2019-12-23
Requirement status
Adoption depends on the project
Sources, edition & access

Technical requirements and test methods for immersion liquid cooling server system of data center

Full text requires authorized access · The official record provides a licensed access link. Only metadata and a summary are included here; this site does not mirror the full standard.

  1. National Library of Standards: T/CCSA 272-2019 ↗

    The specific record marks the standard as current, with both issue and effective dates of 2019-12-23, and describes immersion-cooled servers, supporting operating conditions, and applicability to design, construction, deployment, operation and maintenance.

Official referenceChecked 2026-11-01
China / Association standardCurrent

T/CA 307-2023

Technical requirements and testing specifications for fluorocarbon coolant in data center immersion liquid cooling systems

China Communications Industry Association

Cooling & thermal managementTesting & measurementOperations & acceptance

Specifies technical requirements and test methods for fluorocarbon coolants used in data center immersion liquid cooling. It supports development, production, selection, use and quality verification of this coolant category.

Reading note

Select coolant specifications for the actual fluid category; fluorocarbon requirements should not be applied indiscriminately to all fluids.

Published
2023-12-11
Effective
2024-01-01
Requirement status
Adoption depends on the project
Sources, edition & access

Technical requirements and testing specifications for fluorocarbon coolant in data center immersion liquid cooling systems

Full text requires authorized access · The National Library of Standards provides an official record and a licensed purchase link. This entry covers the edition formally issued in 2023, distinguished from the 2022 project initiation announcement.

  1. National Library of Standards: T/CA 307-2023 ↗

    The specific record marks the standard as current, issued on 2023-12-11 and effective from 2024-01-01; its scope is limited to development, production and use of fluorocarbon coolants for immersion liquid cooling.

Official referenceChecked 2026-11-01
China / Association standardCurrent

T/CAEE 070-2026

Data center liquid cooling blind mating quick connectors - Part 2: Performance requirements and test methods

China Association for Electronic Equipment Technology Development

Cooling & thermal managementDesign & constructionTesting & measurement

Specifies mechanical, sealing, environmental resistance, flow and service-life performance requirements and test methods for blind-mate quick connectors used in data center liquid cooling. It covers applications with water, aqueous ethylene glycol, fluorinated fluids and mineral oils.

Reading note

Check sealing, interchangeability and durability tests against the actual working fluid when accepting quick connectors.

Published
2026-06-02
Effective
2026-06-02
Requirement status
Adoption depends on the project
Sources, edition & access

Data center liquid cooling blind mating quick connectors - Part 2: Performance requirements and test methods

Official record · Provides the official record. The platform posting date is 2026-06-05; both the formal issue date and the effective date are 2026-06-02.

  1. National Platform for Association Standards Information: T/CAEE 070-2026 ↗

    The platform marks the standard as current, with both formal issue and effective dates of 2026-06-02; it was posted on the platform on 2026-06-05, and its scope lists performance requirements, fluids and applicable conditions.

Official referenceChecked 2026-11-01
International & overseas / International standard / technical specificationCurrent

ISO/IEC 22237-1:2021

Information technology — Data centre facilities and infrastructures — Part 1: General concepts

International Organization for Standardization (ISO) / International Electrotechnical Commission (IEC), international standards bodies

Design & constructionEnergy efficiency & carbonOperations & acceptance

Establishes terminology, reference models and general principles for data center facilities. It organizes classifications by availability, security and support for energy efficiency, linking them to life-cycle risk and operational management.

Reading note

Use it as the starting point for facility design, classification and selection of standards across disciplines.

Published
2021-10-05
Effective
No separate effective date listed
Requirement status
Adoption depends on the project
Sources, edition & access

Information technology — Data centre facilities and infrastructures — Part 1: General concepts

Full text requires authorized access · The official abstract and preview are available; the full standard requires an authorized purchase through ISO/IEC. This site provides a Chinese reading-guide translation of the title.

  1. ISO/IEC 22237-1:2021 — Official ISO Record ↗

    First edition, published in 2021-10; the lifecycle shows entry into published stage 60.60 on 2021-10-05, replacing the 2018 Technical Specification.

Official referenceChecked 2026-10-31
International & overseas / International standard / technical specificationCurrent

ISO/IEC 22237-3:2021

Information technology — Data centre facilities and infrastructures — Part 3: Power distribution

International Organization for Standardization (ISO) / International Electrotechnical Commission (IEC), international standards bodies

Power supply & distributionDesign & constructionTesting & measurement

Specifies requirements and recommendations for data center power supplies and internal distribution, including supply and distribution systems, equipotential bonding, lightning protection, and electricity consumption and power quality metering. It also relates these requirements to availability classifications.

Reading note

Review power distribution selection and metering together; redundancy equipment counts alone do not establish the classification.

Published
2021-10-05
Effective
No separate effective date listed
Requirement status
Adoption depends on the project
Sources, edition & access

Information technology — Data centre facilities and infrastructures — Part 3: Power distribution

Full text requires authorized access · The official record provides the abstract and edition information; the full standard requires an authorized purchase.

  1. ISO/IEC 22237-3:2021 — Official ISO Record ↗

    The first edition is published, with a lifecycle publication date of 2021-10-05; it covers supply, distribution, bonding, lightning protection and electricity metering, but excludes safety and electromagnetic compatibility regulations.

Official referenceChecked 2026-10-31
International & overseas / International standard / technical specificationCurrent

ISO/IEC 22237-4:2021

Information technology — Data centre facilities and infrastructures — Part 4: Environmental control

International Organization for Standardization (ISO) / International Electrotechnical Commission (IEC), international standards bodies

Cooling & thermal managementDesign & constructionOperations & acceptance

Specifies controls for temperature, fluid movement, relative humidity, particulates and vibration, together with physical security for environmental control systems. Requirements follow the data center classifications for availability, security and support for energy efficiency.

Reading note

Check airflow or liquid-flow arrangements, humidity, contamination control and system availability together in cooling design.

Published
2021-10-29
Effective
No separate effective date listed
Requirement status
Adoption depends on the project
Sources, edition & access

Information technology — Data centre facilities and infrastructures — Part 4: Environmental control

Full text requires authorized access · The official abstract and preview link are public; the full standard requires an authorized purchase.

  1. ISO/IEC 22237-4:2021 — Official ISO Record ↗

    The first edition was published in 2021-10, with a lifecycle publication date of 2021-10-29; it covers temperature control, fluid movement, humidity, particulates, vibration and physical security.

Official referenceChecked 2026-10-31
International & overseas / International technical specificationCurrent

ISO/IEC TS 22237-7:2018

Information technology — Data centre facilities and infrastructures — Part 7: Management and operational information

International Organization for Standardization (ISO) / International Electrotechnical Commission (IEC), international standards bodies

Operations & acceptanceEnergy efficiency & carbonDesign & construction

Specifies data center management and operational processes, emphasizing resilience, availability, risk mitigation, capacity planning, security and energy efficiency. It links management processes to current and future user requirements.

Reading note

Cite the 2018 Technical Specification for now; the subsequent DIS draft is not a published replacement.

Published
2018-05
Effective
No separate effective date listed
Requirement status
Adoption depends on the project
Sources, edition & access

Information technology — Data centre facilities and infrastructures — Part 7: Management and operational information

Full text requires authorized access · The full Technical Specification requires an authorized purchase; the official publication date is given only to month precision, 2018-05. To be revised does not mean superseded, and the TS designation must be retained.

  1. ISO/IEC TS 22237-7:2018 — Official ISO Record ↗

    The official record labels it a published Technical Specification at stage 90.92, to be revised; it explicitly states that this edition remains valid while the subsequent ISO/IEC DIS 22237-7 is under development.

Official referenceChecked 2026-10-31
International & overseas / International standard / technical specificationCurrent

ISO/IEC 30134-2:2026

Information technology — Data centres key performance indicators — Part 2: Power usage effectiveness (PUE)

International Organization for Standardization (ISO) / International Electrotechnical Commission (IEC), international standards bodies

Energy efficiency & carbonTesting & measurementOperations & acceptance

Defines PUE and specifies measurement categories, calculation, reporting and interpretation. The second edition updates boundary treatment for mixed-use buildings, unmetered energy and on-site generation, together with related measurement requirements.

Reading note

Use the 2026 second edition when citing the international PUE methodology and state the measurement boundary and reporting period.

Published
2026-01-16
Effective
No separate effective date listed
Requirement status
Adoption depends on the project
Sources, edition & access

Information technology — Data centres key performance indicators — Part 2: Power usage effectiveness (PUE)

Full text requires authorized access · The official abstract and preview are available; the full text requires an authorized purchase. The 2016 edition is no longer presented as current.

  1. ISO/IEC 30134-2:2026 — Official ISO Record ↗

    The second edition is published, with a lifecycle publication date of 2026-01-16; both the 2016 edition and its 2018 amendment are listed as withdrawn.

  2. ISO/IEC 30134-2:2026 — Official IEC Webstore ↗

    Confirms edition 2.0 and publication on 2026-01-16; the standard specifies PUE measurement, calculation, reporting and correct interpretation.

Official referenceChecked 2026-10-31
International & overseas / International standard / technical specificationCurrent

ISO/IEC 30134-3:2016 + Amd 1:2018

Information technology — Data centres — Key performance indicators — Part 3: Renewable energy factor (REF)

International Organization for Standardization (ISO) / International Electrotechnical Commission (IEC), international standards bodies

Energy efficiency & carbonTesting & measurementOperations & acceptance

Defines the renewable energy factor for data centers and specifies its calculation, presentation and correct interpretation. Consult the published Amendment 1:2018 alongside the base standard for the complete methodology.

Reading note

Report REF, which describes renewable energy use, separately from energy efficiency metrics such as PUE.

Published
2016-04-19
Effective
No separate effective date listed
Requirement status
Adoption depends on the project
Sources, edition & access

Information technology — Data centres — Key performance indicators — Part 3: Renewable energy factor (REF)

Full text requires authorized access · Both the full base standard and its amendment require authorized access. ISO states that amendment content is not automatically incorporated into the original standard text.

  1. ISO/IEC 30134-3:2016 — Official ISO Record ↗

    The first edition is published and explicitly remains current; it is at stage 90.20, systematic review, in 2026, and the record also lists one amendment from 2018.

  2. ISO/IEC 30134-3:2016/Amd 1:2018 — Official ISO Record ↗

    Amendment 1:2018 is published and explicitly applies to ISO/IEC 30134-3:2016.

Official referenceChecked 2026-10-31
International & overseas / International standard / technical specificationCurrent

ISO/IEC 30134-6:2021

Information technology — Data centres key performance indicators — Part 6: Energy Reuse Factor (ERF)

International Organization for Standardization (ISO) / International Electrotechnical Commission (IEC), international standards bodies

Energy efficiency & carbonCooling & thermal managementTesting & measurement

Uses the energy reuse factor to quantify reuse of energy consumed by a data center. It defines the ratio of reused energy to total data center energy consumption for performance accounting, including waste heat utilization.

Reading note

Record exported waste heat separately within the ERF accounting boundary, stating its end use and measurement period.

Published
2021-08-11
Effective
No separate effective date listed
Requirement status
Adoption depends on the project
Sources, edition & access

Information technology — Data centres key performance indicators — Part 6: Energy Reuse Factor (ERF)

Full text requires authorized access · The official abstract is public; the full text requires an authorized purchase. The current published edition is under revision, and the AWI project is not a published new edition.

  1. ISO/IEC 30134-6:2021 — Official ISO Record ↗

    The first edition is published, with a lifecycle publication date of 2021-08-11; it entered stage 90.92, to be revised, on 2026-05-22, while the subsequent AWI remains under development.

Official referenceChecked 2026-10-31
International & overseas / International standard / technical specificationCurrent

ISO/IEC 30134-7:2023

Information technology — Data centres key performance indicators — Part 7: Cooling efficiency ratio (CER)

International Organization for Standardization (ISO) / International Electrotechnical Commission (IEC), international standards bodies

Cooling & thermal managementEnergy efficiency & carbonTesting & measurement

Uses the cooling efficiency ratio to quantify the energy efficiency of systems controlling the temperature of data center spaces. It specifies measurement, calculation, reporting and interpretation, and explains relationships with other metrics and influencing parameters.

Reading note

CER complements PUE when assessing cooling, but excludes systems such as non-electrically driven absorption cooling.

Published
2023-03-10
Effective
No separate effective date listed
Requirement status
Adoption depends on the project
Sources, edition & access

Information technology — Data centres key performance indicators — Part 7: Cooling efficiency ratio (CER)

Full text requires authorized access · The official record provides the scope and preview; the full standard requires an authorized purchase.

  1. ISO/IEC 30134-7:2023 — Official ISO Record ↗

    The first edition is published, with a lifecycle publication date of 2023-03-10; the abstract explicitly excludes non-electrically driven cooling systems.

Official referenceChecked 2026-10-31
International & overseas / International standard / technical specificationCurrent

ISO/IEC 30134-8:2022

Information technology — Data centres key performance indicators — Part 8: Carbon usage effectiveness (CUE)

International Organization for Standardization (ISO) / International Electrotechnical Commission (IEC), international standards bodies

Energy efficiency & carbonTesting & measurementOperations & acceptance

Uses carbon usage effectiveness to quantify carbon dioxide emissions intensity during the use phase of a data center's life cycle. It specifies measurement categories, calculation and reporting, and relates the metric to infrastructure and IT operation.

Reading note

CUE addresses operational emissions and does not replace whole-life carbon accounting for construction and equipment manufacturing.

Published
2022-03-24
Effective
No separate effective date listed
Requirement status
Adoption depends on the project
Sources, edition & access

Information technology — Data centres key performance indicators — Part 8: Carbon usage effectiveness (CUE)

Full text requires authorized access · The official abstract and edition information are public; the full standard requires an authorized purchase.

  1. ISO/IEC 30134-8:2022 — Official ISO Record ↗

    The first edition is published, with a lifecycle publication date of 2022-03-24; its scope explicitly addresses CO2 emissions intensity during the data center use phase.

Official referenceChecked 2026-10-31
International & overseas / International standard / technical specificationCurrent

ISO/IEC 30134-9:2022

Information technology — Data centres key performance indicators — Part 9: Water usage effectiveness (WUE)

International Organization for Standardization (ISO) / International Electrotechnical Commission (IEC), international standards bodies

Water resourcesTesting & measurementOperations & acceptance

Defines water usage effectiveness during the data center use phase. It specifies measurement categories, calculation, reporting and interpretation of water-use intensity, and relates the metric to facilities, IT equipment and operation.

Reading note

Before comparing WUE, state the water-consumption boundary, measurement category and reporting period, and distinguish water withdrawal from water consumption.

Published
2022-03-24
Effective
No separate effective date listed
Requirement status
Adoption depends on the project
Sources, edition & access

Information technology — Data centres key performance indicators — Part 9: Water usage effectiveness (WUE)

Full text requires authorized access · The official abstract is available; the full text requires an authorized purchase. The subsequent CD draft is not treated as a current new edition.

  1. ISO/IEC 30134-9:2022 — Official ISO Record ↗

    The first edition is published, with a lifecycle publication date of 2022-03-24; it is currently at stage 90.92, to be revised, while the subsequent ISO/IEC CD 30134-9 remains under development.

Official referenceChecked 2026-10-31
International & overseas / Overseas standardCurrent

ANSI/TIA-942-C:2024

Telecommunications Infrastructure Standard for Data Centers

Telecommunications Industry Association (TIA), United States; approved under American National Standards Institute (ANSI) procedures

Design & constructionPower supply & distributionCooling & thermal managementOperations & acceptance

Covers infrastructure for data centers of different sizes and types, including telecommunications, buildings, electrical supply and distribution, cooling, fire protection, physical security and monitoring. It updates requirements for space, load-bearing capacity, cabinets and related provisions.

Reading note

As TIA-942-C is a United States standard, check its Rated classifications and discipline-specific design requirements against the project's adopted scope.

Published
2024-05
Effective
No separate effective date listed
Requirement status
Adoption depends on the project
Sources, edition & access

Telecommunications Infrastructure Standard for Data Centers

Full text requires authorized access · Obtain the full standard through TIA's official purchase link. The publication date is known to month precision; mandatory adoption for a project depends on local regulations, contracts or certification requirements.

  1. TIA-942 — Official TIA Standards Directory ↗

    The official directory identifies revision C as current; it covers data center infrastructure, with revisions affecting telecommunications, power, cooling, buildings, fire protection and security.

  2. TIA Unveils Revision C — Official TIA Publication Announcement ↗

    The announcement dated 2024-05-09 confirms publication of revision C and describes changes from revision B.

  3. ANSI/TIA-942-C — Official TIA Fiber Optics Tech Consortium Explanation ↗

    Confirms publication in 2024-05; use of the rating system itself is not mandatory, but the corresponding rating tables are normative when the system is adopted.

Official referenceChecked 2026-10-31
International & overseas / Overseas standardIn development / draft

ANSI/TIA-942-C Addendum 1 (project under development)

Addendum 1: Artificial Intelligence to ANSI/TIA-942-C

Telecommunications Industry Association (TIA), United States; Technical Subcommittee TR-42.1

Design & constructionPower supply & distributionCooling & thermal management

This addendum under development is intended to address infrastructure for AI and high-performance computing, including high-density, high-speed cabling, power and cooling. Its scope includes investigation of emerging power and heat-removal approaches such as liquid cooling.

Reading note

The addendum is only an initiated project, with TIA targeting publication in mid-2027, and cannot yet serve as a published acceptance criterion.

Published
Official date to be confirmed
Effective
No separate effective date listed
Requirement status
Adoption depends on the project
Sources, edition & access

Addendum 1: Artificial Intelligence to ANSI/TIA-942-C

Official record · Provides the official project initiation and expected schedule; no published final addendum text is available. The designation follows the official project wording, without inventing a final year or standard number.

  1. TIA Advances AI Ready Data Centers — Official TIA Announcement ↗

    The announcement dated 2026-03-24 explicitly states that a project to develop the addendum has been initiated and that publication is targeted for mid-2027; launch wording in the headline does not establish formal publication.

Official referenceChecked 2026-10-31
International & overseas / Overseas standardCurrent

ANSI/ASHRAE 90.4-2025

Energy Standard for Data Centers

American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE); approved by the American National Standards Institute (ANSI)

Energy efficiency & carbonPower supply & distributionCooling & thermal managementDesign & construction

Specifies minimum energy efficiency requirements for new data centers, extensions and alterations to existing data center systems, addressing design, construction, and planned operation and maintenance. It also considers related environmental factors, including energy, water use and greenhouse gases.

Reading note

The 2025 edition supersedes the 2022 edition; check applicability, the latest addenda and errata, and local adoption before use.

Published
Official date to be confirmed
Effective
No separate effective date listed
Requirement status
Adoption depends on the project
Sources, edition & access

Energy Standard for Data Centers

Full text requires authorized access · An official read-only preview is available; authorized copies require purchase. The exact publication day has not been verified and is left blank. This is a United States standard, not an ISO international standard.

  1. Titles, Purposes, and Scopes — Official ASHRAE Directory ↗

    Explicitly states that ANSI/ASHRAE Standard 90.4-2025 is published and supersedes 90.4-2022, and lists its purpose and scope.

  2. Preview ASHRAE Standards and Guidelines — Official ASHRAE Read-only Preview ↗

    The current popular standards section lists 90.4-2025 and provides official read-only viewing and purchase links.

Official referenceChecked 2026-10-31
International & overseas / Technical guidance & open specificationsCurrent

ASHRAE TC 9.9 Datacom Encyclopedia — Thermal Guidelines (online)

Thermal Guidelines for Data Processing Environments — ASHRAE TC 9.9 Datacom Encyclopedia

American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE); Technical Committee 9.9

Cooling & thermal managementDesign & constructionOperations & acceptance

Provides guidance on thermal environmental limits for data center IT equipment and on facility operation. The TC 9.9 online encyclopedia continuously updates material from the earlier Thermal Guidelines and retains previous book editions for historical reference.

Reading note

Engineering citations should state the online access date and equipment category; page references to older books do not identify the current online content.

Published
Official date to be confirmed
Effective
No separate effective date listed
Requirement status
Adoption depends on the project
Sources, edition & access

Thermal Guidelines for Data Processing Environments — ASHRAE TC 9.9 Datacom Encyclopedia

Full text requires authorized access · The online encyclopedia requires a paid subscription. This entry covers a continuously updated guidance topic, not a newly numbered standard; the revised and expanded fifth-edition book is historical background. This site does not mirror the books, reference card or subscription content.

  1. Official ASHRAE TC 9.9 Website and Datacom Encyclopedia Explanation ↗

    The official explanation states that the online encyclopedia has replaced the earlier books, includes updated Thermal Guidelines material, and preserves PDFs of previous book editions for historical reference.

  2. ASHRAE Data Center Resources — Official Resource Portal ↗

    Developed from 2024 onward, the online encyclopedia brings together frequently updated guidance on facilities, equipment, environments and cooling, available by annual subscription.

  3. Thermal Guidelines Fifth Edition, Revised and Expanded — Official ASHRAE Reference Card ↗

    The reference card identifies the historical book as the revised and expanded fifth edition, with copyright years 2021 and 2024; the card is not the complete current online guidance.

Official referenceChecked 2026-10-31
International & overseas / Technical guidance & open specificationsCurrent

ASHRAE TC 9.9 Datacom Encyclopedia — Liquid Cooling Guidelines (online)

Liquid Cooling Guidelines for Datacom Equipment Centers — ASHRAE TC 9.9 Datacom Encyclopedia

American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE); Technical Committee 9.9

Cooling & thermal managementWater resourcesDesign & constructionOperations & acceptance

Updates the earlier Liquid Cooling Guidelines online, covering TCS supply-liquid temperature S classes, differences between TCS and facility water-system quality requirements, cold-plate and immersion system design, and liquid cooling retrofits of existing air-cooled facilities.

Reading note

Consult the updated online material for liquid cooling design rather than relying solely on the 2013 second edition and its earlier temperature classifications.

Published
Official date to be confirmed
Effective
No separate effective date listed
Requirement status
Adoption depends on the project
Sources, edition & access

Liquid Cooling Guidelines for Datacom Equipment Centers — ASHRAE TC 9.9 Datacom Encyclopedia

Full text requires authorized access · Access the current updated material through an annual subscription to the TC 9.9 online encyclopedia; the 2013 second edition is a historical book. This entry is technical guidance, not an ISO standard or an ANSI-numbered standard.

  1. Official ASHRAE TC 9.9 Website — Liquid Cooling Guidelines Update ↗

    The official explanation states that almost all of the earlier Liquid Cooling Guidelines content has been rewritten, adding TCS supply-liquid S classes, water-quality boundaries, cold-plate and immersion design, and air-cooled facility retrofit guidance.

  2. Liquid Cooling Guidelines, Second Edition Errata — Official ASHRAE Historical Record ↗

    The official errata identify 2013 as the second-edition book's publication year and 2014-09-11 as the errata update date, providing evidence for identifying the historical edition.

Official referenceChecked 2026-10-31
International & overseas / Technical guidance & open specificationsCurrent

OCP Project Deschutes V1.0.0

Project Deschutes: Data Center Facilities V.1.0.0

Open Compute Project Foundation (OCP), United States; contributed by Google

Cooling & thermal managementPower supply & distributionDesign & constructionOperations & acceptance

An open CDU reference specification for liquid-cooled facilities, including high-density AI deployments. It covers coolant distribution units and related facility interfaces, design requirements and verification methods, providing a common basis for product development across suppliers.

Reading note

Use it as an open reference for CDU engineering and procurement, while checking interfaces and verification requirements against project operating conditions.

Published
Official date to be confirmed
Effective
2026-02-26
Requirement status
Adoption depends on the project
Sources, edition & access

Project Deschutes: Data Center Facilities V.1.0.0

Official open full text · The official open PDF is directly available and is not mirrored here. Although its metadata title retains DRAFT, status is established by OCP's validated contributions database and official publication statement. It is an industry open technical specification, displayed in the guidance category.

  1. OCP Contributions Database — Official Validated Contributions Directory ↗

    The directory states that listed contributions have undergone comprehensive validation; it explicitly lists Project Deschutes V1.0.0, Google as contributor, the CDU category and publication year 2026.

  2. Project Deschutes V1.0.0 — Official OCP Open PDF ↗

    The official PDF index shows a cover labeled Specification, version 1.0.0 and Effective Feb 26, 2026; the PDF is approximately 21 MB, and its body is not stored on this site.

  3. Realizing the OCP Open Data Center Ecosystem Vision — Official OCP Explanation ↗

    OCP explicitly describes it as the OCP-published version 1.0 Deschutes CDU, corroborating its formal inclusion in the contributions database.

Official referenceChecked 2026-10-31